What is the minimum number of small-appliance circuits permitted by the Code

Goal: Understanding the NEC code language for practical DIY application.

All occurrences of the phrase "no other outlets" related to a house (not an RV) in the NEC 2017 are:

210.11 Branch Circuits Required.

...(C) Dwelling Units.

...(1) Small-Appliance Branch Circuits. In addition to the number of branch circuits required by other parts of this section, two or more 20-ampere small-appliance branch circuits shall be provided for all receptacle outlets specified by 210.52(B).

...(2) Laundry Branch Circuits. In addition to the number of branch circuits required by other parts of this section, at least one additional 20-ampere branch circuit shall be provided to supply the laundry receptacle outlet(s) required by 210.52(F). This circuit shall have no other outlets.

...(3) Bathroom Branch Circuits. In addition to the number of branch circuits required by other parts of this section, at least one 120-volt, 20-ampere branch circuit shall be provided to supply the bathroom(s) receptacle outlet(s). Such circuits shall have no other outlets.

...(4) Garage Branch Circuits. In addition to the number of branch circuits required by other parts of this section, at least one 120-volt, 20-ampere branch circuit shall be installed to supply receptacle outlets in attached garages and in detached garages with electric power. This circuit shall have no other outlets.

210.52 Dwelling Unit Receptacle Outlets. This section provides requirements for 125-volt, 15- and 20-ampere receptacle outlets. [...]

...(A) General Provisions. In every kitchen, family room, dining room, living room, parlor, library, den, sunroom, bedroom, recreation room, or similar room or area of dwelling units, receptacle outlets shall be installed in accordance with the general provisions specified in 210.52(A)(1) through (A)(4) [about spacing etc].

...(B) Small Appliances.

...(1) Receptacle Outlets Served. In the kitchen, pantry, breakfast room, dining room, or similar area of a dwelling unit, the two or more 20-ampere small-appliance branch circuits required by 210.11(C)(1) shall serve all wall and floor receptacle outlets covered by 210.52(A), all countertop outlets covered by 210.52(C), and receptacle outlets for refrigeration equipment.

...(2) No Other Outlets. The two or more small-appliance branch circuits specified in 210.52(B)(1) shall have no other outlets.

625.40 Electric Vehicle Branch Circuit. Each outlet installed for the purpose of charging electric vehicles shall be supplied by an individual branch circuit. Each circuit shall have no other outlets.

These texts confuse me: 210.52(B)(2) applies to the branch circuits of 210.52(B)(1). In turn, 210.52(B)(1) initially includes (something like) only food-related areas, but then extends to receptacle outlets covered by 210.52(A), which includes almost the whole house including the mentioned food areas except, roughly, the pantry and breakfast room.

Questions:

  1. Why is it written like this? What is the intent?
  2. To which spaces/areas does the "No Other Outlet" of 210.52(B)(2) requirement apply?

Example dilemma:

Let's take a new bedroom:

Interpretation 1: This bedroom, INcluding all of its wall receptacle outlets, is covered in 210.52(A). Hence, 210.52(B)(1), by referring to 210.52(A), does require all bedroom wall receptacles to be served by one or more "20A small appliance branch circuits". So no other outlets are allowed.

Interpretation 2: This bedroom, EXcluding all of its wall receptacle outlets, is covered in 210.52(A) (so just the abstract room space; its receptacle outlets are not explicitly mentioned). Hence, 210.52(B)(1), by referring to 210.52(A), does not require all bedroom wall receptacles to be served by one or more "20A small appliance branch circuits". So other outlets are allowed.

Which interpretation is correct?

Related posts:

  • What does “No Other Outlets” mean for a kitchen 20A branch circuit?

Find out what the electrical code says about the circuit requirements for a kitchen and find out why.

The code requires two or more 20-ampere small-appliance branch circuits for all of the receptacle outlets in the kitchen and the areas associated with the kitchen such as pantries, breakfast rooms, dining rooms. The dedicated small-appliance branch circuits are exclusively used for the kitchen wall and countertop receptacles and the ancillary areas and must not be used to supply lighting loads or any other non-kitchen areas.

The reason for this is to ensure that all of the combined capacity of the 20-ampere small-appliance circuits is available for an undetermined number of portable appliances that may be used at any one time by the homeowner. Think about all of the typical portable appliances that may be used for a Thanksgiving get-together: slow-cooker pots, fondue pot, blender, hand mixer, food processor, coffee maker, juicer, toaster oven, waffle maker and more.

Kitchen Circuit Requirements

In the typical kitchen, the receptacle outlets that serve the countertop areas get used much more often than the wall receptacles that may be scattered around the perimeter of the kitchen or dining room area. That is why all of the receptacles that serve the countertop surfaces are required to be supplied by two or more 20-ampere small-appliance branch circuits.

In other words, the receptacles for the countertop surfaces need to be divided between the two or more 20-ampere small-appliance circuits to avoid any overloading conditions that could occur if all of the countertop receptacles were only supplied by one of the 20-ampere small-appliance circuits.

The National Electrical Code (NEC) contains an introduction, nine chapters and eight annexes; Article 90 is the introduction to the NEC, and it includes specifications that are essential to the rest of the Code book. The scope is one item covered in the introduction (in 90.2). Most articles have a scope, but there is a difference between this article and all other articles.

Other articles have a scope that describes what is covered in that particular article. The scope in Article 90 details what the NEC covers and what the NEC does not cover. Also covered in the scope of Article 90 is special permission. As stated in 90.2(C), the authority having jurisdiction (AHJ) is permitted to grant exception for the installation of conductors and equipment that are not under the exclusive control of the electric utilities and are used to connect the electric utility supply system to the service-entrance conductors of the premises served. This special permission provision is only possible if such installations are outside a building or terminate immediately inside a building wall. This is the first of approximately 20 Code sections (in 17 articles) containing the term “special permission.”

The term “special permission” also is in Section 90.4. By special permission, the AHJ may waive specific requirements in the NEC or permit alternative methods where it is assured that equivalent objectives can be achieved by establishing and maintaining effective safety. Because the term is essential to the proper application of the Code and it is used in more than one article, it is defined in Article 100. Special permission is the written consent of the AHJ. It is important to note that special permission is not permission in verbal form only; it must be in writing.

Last month’s article covered the calculated load for general lighting and general-use receptacle in 220.82(B)(1). This month, the discussion continues with optional feeder or service load calculations as specified in 220.82.

There are a limited number of occupancy types that can be calculated by optional methods. Occupancy types include dwelling units (one family, two family and multifamily), schools, and new restaurants. The optional calculation for a single-family dwelling starts out the same as the standard method calculation specified in Part III of Article 220. The first step, covered last month, is calculating the general lighting and general-use receptacle load from the square-foot floor area. The next provision is usually broken down into two steps. In accordance with 220.82(B)(2), each 2-wire, 20-ampere (A) small-appliance branch circuit covered in 210.11(C)(1) must be included into the calculation at 1,500 volt-amperes (VA). To calculate, simply multiply the number of small-appliance branch circuits by 1,500 VA. For example, what is the optional service load calculation (before applying the demand factor) for a single-family dwelling that will have five small-appliance branch circuits? Since there are five small-appliance branch circuits, multiply 1,500 by 5 (1,500 5 = 7,500). Before applying the demand factor in 220.82(B), the calculated load for five small-appliance branch circuits in this dwelling is 7,500 VA (see Figure 1).

Although there is no maximum number of small-appliance branch circuits, there is a minimum. In accordance with 210.11(C)(1), at least two 20A small-appliance branch circuits must be provided for all receptacle outlets required by 210.52(B). In the kitchen, pantry, breakfast room, dining room or similar area of a dwelling unit, the two or more 20A small-appliance branch circuits required by 210.11(C)(1) shall serve all wall and floor receptacle outlets covered by 210.52(A), all countertop outlets covered by 210.52(C), and receptacle outlets for refrigeration equipment [210.52(B)(1)]. Therefore, the minimum number of 2-wire, 20A small-appliance branch circuits is two (see Figure 2).

Before finalizing the number of circuits, ensure that receptacles installed in a kitchen to serve countertop surfaces are supplied by at least two small-appliance branch circuits as required by 210.52(B)(3). Either or both of these circuits also shall be permitted to supply receptacle outlets in the same kitchen and in other rooms specified in 210.52(B)(1).

Also in accordance with 220.82(B)(2), each 2-wire, 20A laundry branch circuit covered in 210.11(C)(2) must be included into the calculation at 1,500 VA. For example, what is the optional service load calculation (before applying the demand factor) for a single-family dwelling that will have two laundry branch circuits? Since there are two laundry branch circuits, multiply 1,500 by 2 (1,500 2 = 3,000). Before applying the demand factor in 220.82(B), the calculated load for two laundry branch circuits in this dwelling is 3,000 VA (see Figure 3).

As stipulated in 210.11(C)(2), at least one additional 20A branch circuit shall be provided to supply the laundry receptacle outlet(s) required by 210.52(F). Section 210.52(F) also states that at least one receptacle outlet must be installed for the laundry. There are two exceptions to 210.52(F), but neither is applicable to a one-family dwelling. While it is not required that a dwelling have a clothes-washing machine, it is required that a receptacle outlet, supplied by a 20A branch circuit, be installed for the laundry. A load calculation for a one-family dwelling must include at least one laundry branch circuit rated 1,500 VA when calculating by the optional method (see Figure 4).

Regardless of the size of a one-family dwelling, it must include at least two 20A small-appliance branch circuits and at least one 20A laundry branch circuit. Regardless of how small the one-family dwelling, at least 4,500 VA must be included in the optional method load calculation: 3,000 VA (1,500 2 = 3,000) for the two small-appliance branch circuits and 1,500 VA for the laundry branch circuit.

Next month’s column continues the discussion of feeder and service load calculations.